Outdoor unit VRV A One-Dimensional Cold Gas R410a – Model: RXQ8BYM | Capacity 76,400 Btu/h

Outdoor unit VRV A Cold One-Dimensional Model RXQ8BYM The product used is the most effective choice for modern commercial buildings and office buildings refrigerant R410a It's eco-friendly, delivers high efficiency and significant power savings 76,400Btu/h (~22.4kW)This device caters to the need for large area cooling with high stability.
Technical specifications Highlights:
-
Model: RXQ8BYM
-
Type: outdoor unit VRV A – cold one - dimensionality
-
Refrigerant: R410a – safe and environmentally friendly
-
Cooling capacity: 76,400 Btu/h (~22.4 kW)
-
Power input: 5.00 kW
-
Dimensions (Size x Width x Depth): 1,660 x 930 x 765 mm
-
Weight: 206 kg
The superiority of outdoor unit VRV A RXQ8BYM:
-
High efficiency: With capacity 22.4kW, the product is ideally suited for medium and large scale central air conditioning systems.
-
Energy efficiency: Inverter technology combined with refrigerant R410a helps to optimize performance and reduce operating costs.
-
Compact, solid design: Easy to install and maintain due to its reasonable size and durable structure.
-
Smooth operation: Noise is minimized and suitable for installation in urban, hotel and office environment.
Applications:
Outdoor unit VRV A RXQ8BYM is widely used in:
-
Office buildings
-
Hotels, resorts
-
Shopping centers
-
Large scale cold storage facilities
Why choose outdoor unit Daikin VRV RXQ8BYM?
Daikin is the leading brand in Japan in the field of air conditioning. RXQ8BYM products inherit advanced technology, high durability and outstanding stability – the perfect solution for professional central air conditioning systems.
Contact me immediately for the best advice and recommendation for outdoor unit VRV A Model RXQ8BYM!
Installation Instructions outdoor unit VRV A RXQ8BYM Technical Correctness
Properly installed technology not only helps outdoor unit VRV RXQ8BYM This is a simple, portable, and cost - effective system that not only works stably but also extends the life of the equipment, ensuring optimal cooling performance. Here are the requirements and considerations required during installation:
1 Ideal Installation Location
-
Installation in place ventilatedAvoid direct sunlight and rain.
-
Do Not Fit In Place has exhaust or corrosive vaporIt's close to chemicals or pollution.
-
Minimum wall spacing:
-
Rear: ≥ 300 mm
-
Forward (wind stream): ≥ 1,000 mm
-
Two sides: ≥ 300 mm each
-
-
Warranty flatnessIt does not shake when operated.
2. Requirements for foundation
-
The foundation must good load to support weight 206kg.
-
It should be on a concrete support or stainless steel bracket, with a rubber seal against vibration.
-
The inclination should not exceed 5 ° to avoid oil leaks.
3 Gas and condensate pipelines
-
Usage standard copper pipe for the gas R410a system, fully insulated.
-
The pipeline length and elevation difference must comply with the manufacturer's instructions (maximum: 165 m length, 50 m elevation between outdoor unit and indoor unit).
-
Suspended sewer design continuous slope and water traps if necessary.
4. Electrical Connections
-
Power supplies: 3 pha – 380V – 50Hz
-
Wiring in the right power diagram, using Separate CB protection... land in accordance with regulations.
-
Do not share power with other heavy - duty load devices.
5 Testing and commissioning
-
Verify gas pressure, seal the pipe before filling it with additional gas.
-
Check the fan rotation, the power surge and test run of the entire system.
-
Warranty no leaksNoise levels are within acceptable limits and cooling temperatures are stable.
Important installation notes:
✅ installation must be done by technician with a certificate VRV of Daikin
✅ Do not change components, gas pipes or power lines without permission
Maintain for every 3 – 6 month to ensure performance
Do you want me to accompany drawing of installation diagrams or list installed for print usage No?